beautypg.com

EVCO EVCSR818P9EF User Manual

Page 68

background image

EVCO S.p.A.

Vcolor 818

| Installer manual ver. 1.1 | Code 144VC818E114

page 68 of 94

d16

0

99

min

0

duration of pre-dripping (only if parameter d1 is set at 1;

the compressor and evaporator fan will be off during pre-

dripping and the defrosting output will remain activated)

Par.

Min.

Max.

Unit

Default

Temperature alarms (9) (10)

A1

0

99

°C/°F (1)

10

cabinet temperature below which the minimum temperature

alarm is activated (relative to the work set-point, i.e. “r10

A1” during post blast chilling storage and “r11 - A1” during

post deep freezing storage; (“AL” code); see also

parameter A11 (4)

A2

0

1

- - - -

1

enabling of minimum temperature alarm (“AL” code)

1 = yes

A4

0

99

°C/°F (1)

10

cabinet

temperature

above

which

the

maximum

temperature alarm is activated (relative to the work set-

point, i.e. “r10 +A4” during post blast chilling storage and

“r11 +A4” during post deep freezing storage; (“AH” code);

see also parameter A11 (4)

A5

0

1

- - - -

1

enabling of maximum temperature alarm (“AH” code)

1 = yes

A7

0

240

min

15

temperature alarm delay (“AL” code and “AH” code)

A8

0

240

min

15

maximum temperature alarm delay (“AH” code) from the

conclusion of evaporator fan stop and storage start-up

A10

0

240

min

5

duration of a power cut such to cause the power cut alarm

to be memorised ( “PF” code)when the power is supplied

0 = the alarm will not be signalled

AA

0

240

s

5

duration of buzzer activation on conclusion of blast chilling

and deep freezing

A11

1

15

°C/°F (1)

2

parameters A1 and A4 differential

A13

0

1

- - - -

1

memorisation of the temperature-controlled blast chilling or

temperature-controlled deep freezing non concluded within

maximum duration alarm (“tiM” code)

1 = yes