EVCO S.p.A.

Vcolor 818

| Installer manual ver. 1.1 | Code 144VC818E114

page 23 of 94

5.1

If the test is completed successfully, the cycle will be started.

The maximum blast chilling duration count is started on condition that the temperature detected by the

needle probe is below that established with parameter r15.

5.2

If the test is not completed successfully, the buzzer will be activated for 5 s every 60 s and the cycle will

be started with timed-control; see paragraph 6.4 "Time-controlled blast chilling and storage".

During blast chilling the device displays the temperature detected by the needle probe, the cabinet temperature, the

program name (if envisioned) and the time passed since the start of blast chilling.

Operate as indicated to stop the cycle:

6.

Press and hold the START/STOP key 3 s.

The successive parameters establish the following values:

-

parameter r3 establishes the blast chilling end temperature

-

parameter r5 establishes the maximum blast chilling duration

-

parameter r7 establishes the work set-point during blast chilling.

If the temperature detected by the needle probe reaches the blast chilling end temperature within the maximum blast

chilling duration, it means that blast chilling has been completed successfully, the device will automatically pass to

storage and the buzzer will be activated for the period of time established with parameter AA.

Press and release a key to silence the buzzer.

During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the time

taken to complete blast chilling successfully.

Parameter r10 establishes the work set-point during storage.

If the temperature detected by the needle probe does not reach the blast chilling end temperature within the maximum

blast chilling duration, blast chilling will not be completed successfully but will continue and the buzzer will be activated.

Press and release a key to restore normal display and to silence the buzzer.

When the temperature detected by the needle probe reaches the blast chilling end temperature, the device

automatically passes to storage in the same way as illustrated previously.