10»5 Empty Pipe Alarm
Proceed as follows to use the empty pipe alarm ouiput.
Alarm output setting
Set the empty alarm enable/disabJe Mates la ON. Sec iS.2*l3, “Hmpty Pipe Alarm.'’
DO function i^tting
Set DOl or D02 (option) as ;hc empty pipe alarm output, and select liie active
status, Normal Open or Normal Cfose. See B.2.9, “Digital I/O” If you use the empty
pipe alarm function but not an external output, this setting is not needed.
Output conditions when an empty pipe aliirm occurs:
• 4-20nA output:
4inA .
Note: In case nf the converter for special specifications (refer to 733
“Converter for Special specificationsselect the value which
be sel 4-20mA Alarm Output.
For dciaih see Sec 82, lS”4-20mA Alarm Output
• Totalizer arid pulse outputiTotalizcr and pulse output arc stopped.
• Measured data display:
Zero is indicated for instantaneous flow rate.
• Alarm output:
Condition programmed in the Digital output function and
active status set.
Note: Alarm output contacts are open while the converter is powered off.
See tihaptcr 12, “Sdf-Diagnostics and Warning Functions." to use the empty pipe alarm
function.
-