beautypg.com

Completing the installation, Checking the installation, Chapter 6 – Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 51: Chapter

background image

Rockwell Automation Publication D2-3518-3 - May 2013

51

Chapter

6

Completing the Installation

This chapter provides instructions on how to perform a final check of the
installation before power is applied to the drive.

Checking the Installation

Use the following procedure to verify the condition of the installation:

1.

Turn off, lock out, and tag the input power to the drive. Wait 5 minutes.

2.

Verify that the DC bus voltage is zero. See

Verify that the DC Bus

Capacitors are Discharged Before Servicing the Drive on page 195

.

3.

Remove any debris, such as metal shavings, from around the drive.

4.

Check that there is adequate clearance around the drive.

5.

Verify that the wiring to the terminal strip and the power terminals is
correct.

6.

Check that the wire size is within terminal specifications and that the wires
are tightened properly.

7.

Check that user-supplied branch circuit protection is installed and
correctly rated.

ATTENTION: Only qualified electrical personnel familiar with the construction
and operation of this equipment and the hazards involved should start and
adjust it. Read and understand this manual in its entirety before proceeding.
Failure to observe this precaution could result in severe bodily injury or loss of
life.

ATTENTION: DC bus capacitors retain hazardous voltages after input power has
been disconnected. After disconnecting input power, wait 5 minutes for the DC
bus capacitors to discharge and then check the voltage with a voltmeter to
ensure the DC bus capacitors are discharged before touching any internal
components. Failure to observe this precaution could result in severe bodily
injury or loss of life.

ATTENTION: You must provide an external, hardwired emergency stop circuit
outside of the drive circuitry. This circuit must disable the system in case of
improper operation. Uncontrolled machine operation may result if this
procedure is not followed. Failure to observe this precaution could result in
bodily injury.