Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual
Page 160

160
Rockwell Automation Publication D2-3518-3 - May 2013
Chapter 9
Sets the user-configurable digital output activation level for options 10...15 in
Digital Out1 Sel. Units are assumed to match the above selection (for example,
At Freq = Hz, At Torque = Amps).
See
AC Line I/O Board Description (Frame 3 Only) on page 25
through
Combined I/O Board Description (Frame 4 Only) on page 29
for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
Sets the on delay time for user-configurable digital output 1. This is the time
between the occurrence of a condition and activation of the user-configurable
digital output.
See
AC Line I/O Board Description (Frame 3 Only) on page 25
through
Combined I/O Board Description (Frame 4 Only) on page 29
for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
Sets the off delay time for user-configurable digital output 1. This is the time
between the disappearance of a condition and de-activation of the user-
configurable digital output.
See
AC Line I/O Board Description (Frame 3 Only) on page 25
through
Combined I/O Board Description (Frame 4 Only) on page 29
for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
381
Dig Out1 Level
Range:
0.0...819.2 [0.1]
Default:
0.0
Access:
0
Path: Inputs & Outputs > Digital Outputs
See also:
380
382
Dig Out1 OnTime
Range:
0.00...600.00 sec [0.01 sec]
Default:
0.00 sec
Access:
1
Path: Inputs & Outputs > Digital Outputs
See also:
380
383
Dig Out1 OffTime
Range:
0.00...600.00 sec [0.01 sec]
Default:
0.00 sec
Access:
1
Path: Inputs & Outputs > Digital Outputs
See also:
380