Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual
Page 212

212
Rockwell Automation Publication D2-3518-3 - May 2013
Chapter 10
Power Loss
3
1
3
Input power unavailable or AC line synchronization not possible
for longer than inverter Power Loss Time (185). Enable/disable
with inverter Fault Config 1 (238).
1. Monitor the incoming AC line for low voltage or line power interruption.
2. Check AC line voltage feedback wiring and signal path. This includes the
Combined I/O board and the Combined Control board.
Power Phased ACB
239
4 Input power is phased ACB rather than ABC.
Switch two of the input power phases.
Precharge Closed
233
4 One or more precharge contactors was closed when it should
be open.
1. Check AUX contacts on precharge contactor(s).
2. Check bit 15 in rectifier parameter Dig In Status (216) to view status of
input.
3. Check wiring.
Precharge Opened
234
4 One or more precharge contactors was open when it should be
closed.
1. Check AUX contacts on precharge contactor(s).
2. Check bit 15 in rectifier parameter Dig In Status (216) to view status of
input.
3. Check wiring.
Pwr Brd Chksum1
104
4 The checksum read from the Combined Power board inverter
EEPROM does not match the checksum calculated from the
EEPROM status data.
Clear the fault or cycle power to the drive.
Pwr Brd Chksum2
105
2 The checksum read from the Combined Power board inverter
EEPROM does not match the checksum calculated from the
EEPROM configuration data.
1. Check connections between Combined Control board and Combined
Power board. If this fixes the problem, use inverter Reset To Defaults
(inverter 197) and rectifier Reset To Defaults (rectifier 197) to reset all
drive parameters to defaults, then reconfigure drive as necessary.
2. If problem persists, replace power board.
Rctfr Base Temp
217
4 Measured temperature of one of the rectifier IGBT modules
exceeded limits.
Check for proper temperature and flow rate of coolant.
Rctfr Checksum
229
4 The parameter checksum read from the rectifier portion of the
control board does not match the checksum calculated, or the
control board or power board has been replaced.
1. Clear fault.
2. If fault persists, restore defaults on rectifier (rectifier parameter 197), then
reprogram rectifier parameters.
3. If fault still persists, replace control board or power board.
Rctfr DPI Comm
246
4 DPI communications interrupted between inverter and
rectifier.
1. Clear fault.
2. If fault recurs or persists, replace control board.
Rctfr Dsat
R+, S+, T+
208
209
210
4 High current was detected in an IGBT.
1. Check for loose connection in IGBT wire harness.
2. Check IGBTs.
Rctfr Dsat
R-, S-, T-
241
242
243
4 High current was detected in an IGBT.
1. Check for loose connection in IGBT wire harness.
2. Check IGBTs.
Rctfr Gate Kill
240
4 Gate kill contact is open.
Close gate kill contact.
Rctfr Gnd Fault
216
4 Excessive line side (input) ground current measured.
Check for grounded input wiring.
Rctfr HW Unk
231
4 Rectifier portion of power structure hardware reported
unexpected fault.
1. Verify connections between control board and power board.
2. If fault persists, replace power board.
3. If fault still persists, replace control board.
Rctfr I2T Ovrld
220
4 Long-term current rating of rectifier exceeded.
1. Low input voltage can result in increased current load. Provide proper
input voltage to the drive.
2. Verify that rectifier Input Load Amps (106) is set correctly.
Rctfr IGBT Temp
218
4 Excessive calculated rectifier IGBT junction temperature. See
rectifier Rctfr IGBT Temp (rectifier 19).
Check for proper temperature and flow rate of coolant.
Rctfr IO Board
236
4 Communication between control board and I/O board has not
been established.
1. Clear fault.
2. If fault persists, verify connection between I/O board and control board.
3. If fault still persists, replace I/O board.
4. If fault still persists, replace control board.
Rctfr IT Overld
219
4 Short-term current rating of rectifier exceeded.
Low input voltage can result in increased current load. Provide proper input
voltage to the drive.
Rctfr Not Login
238
4 Rectifier took too long to connect to inverter.
1. Verify the DPI Data Rate (270) is set to 500K.
2. Connect one DPI device at a time to see if one of the DPI devices is causing
the problem.
3. Replace the Combined Control board.
Table 22 - Fault Descriptions and Corrective Actions (Frame 4) (Continued)
Fault
No
.
Ty
pe
Description
Action