Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual
Page 170

170
Rockwell Automation Publication D2-3518-3 - May 2013
Chapter 9
Defines the allowed power dip time that will not cause a Ride Thru Abort fault
(fault 221).
•
Setting a value of 0 generates a fault on a loss of a single line cycle.
•
Setting a value of 0.10 allows line synchronization to be lost for 100 msec
before a fault is generated.
A fault is also generated if the bus voltage drops below the power loss threshold
before the ride-through time has elapsed.
The commanded state of the rectifier.
Frame 3 drives (firmware version 1.x) only:
Figure 68 - Rectifier Control (100) Frame 3
65
Ride Through Sec
Range:
0.00...60.00 seconds [x.xx seconds]
Default:
1.00
Access:
0
Path: Configuration > AC Line
See also:
64, inverter 184, 185
100
Rectifier Contrl
Range:
See
and
Default:
N/A
Access:
0
Path: Dynamic Control > Control and Status
See also:
inverter 33
IMPORTANT
This parameter is used for communication between the inverter and the
rectifier. Do not write to this parameter using VS Utilities, DriveExplorer, or an
OIM. Its value changes according to the operational state of the drive.
x
x
x
0
0
1
1
2
3
4
5
6
7
8
9
11
12
13
14
15
x =Reserved
Bit #
AC
Line I/O:
Dig.
Output 1
AC
Line I/O:
Dig.
Output
2
AC
Line
I/O:
Dig.
Output 3
AC
Line I/O:
Dig.
Output 4
AC
Line I/O:
Dig.
Output 5
AC
Line I/O
: Dig.
Output 6
Close Pre-charge
Enab
le Rectifie
r
Reset Recifier Fau
lt
Inverter Fault
Network Loss
DC Bus Limit
Extend
Nibble 1
Nibble 2
Nibble 3
Nibble 4