Chapter 10
Power Loss
3
1
3
Input power unavailable or AC line synchronization not
possible for longer than inverter Power Loss Time (185).
Enable/disable with inverter Fault Config 1 (238).
1. Monitor the incoming AC line for low voltage or line power interruption.
2. Check AC line voltage feedback wiring and signal path. This includes the line
synchronization board, the AC Line I/O board, and the rectifier control board.
Power Phased ACB
239
4 Input power is phased ACB rather than ABC.
Switch two of the input power phases.
Precharge Closed
233
4 One or more precharge contactors was closed when it
should be open.
1. Check AUX contacts on precharge contactor(s).
2. Check bit 0 in rectifier parameter Dig In Status (216) to view status of input.
3. Check wiring.
Precharge Open
234
4 One or more precharge contactors was open when it
should be closed.
1. Check AUX contacts on precharge contactor(s).
2. Check bit 0 in rectifier parameter Dig In Status (216) to view status of input.
3. Check wiring.
Pwr Brd Chksum1
104
4 The checksum read from the inverter power interface
board EEPROM does not match the checksum calculated
from the EEPROM status data.
Clear the fault or cycle power to the drive.
Pwr Brd Chksum2
105
2 The checksum read from the inverter power interface
board EEPROM does not match the checksum calculated
from the EEPROM configuration data.
1. Check connections between inverter control board and inverter power
interface board. If this fixes the issue, then use inverter Reset To Defaults
(inverter 197) to reset the rectifier to its defaults, then reconfigure the drive as
needed.
2. If problem persists, replace inverter power interface board.
Rctfr Base Temp
217
4 Measured temperature of one of the rectifier IGBT modules
exceeded limits.
Check for proper temperature and flow rate of coolant.
Rctfr Checksum
229
4 The parameter checksum read from the rectifier control
board does not match the checksum calculated, or the
rectifier power board or rectifier control board has been
replaced.
1. Clear fault.
2. If fault persists, restore defaults on rectifier (rectifier parameter 197), then
reprogram rectifier parameters.
3. If fault still persists, replace rectifier control board or rectifier power board.
Rctfr Dsat R, S, T
208
209
210
4 High current was detected in an IGBT.
1. Check for loose connection in IGBT wire harness.
2. Check IGBTs.
Rctfr Gnd Fault
216
4 Excessive input ground current measured.
Check for grounded input wiring.
Rctfr HW Unk
231
4 Rectifier portion of power structure hardware reported
unexpected fault.
1. Verify connection between rectifier control board and rectifier power board.
2. If fault persists, replace rectifier power board.
3. If fault still persists, replace rectifier inverter control board.
Rctfr HW Unused
215
4 Rectifier portion of power structure hardware reported
unexpected fault.
1. Verify connection between rectifier control board and rectifier power board.
2. If fault persists, replace rectifier power board.
3. If fault still persists, replace rectifier inverter control board.
Rctfr I2T Ovrld
220
4 Long-term current rating of rectifier exceeded.
1. Low input voltage can result in increased current load. Provide proper input
voltage to the drive.
2. Verify that rectifier Input Load Amps (106) is set correctly.
Rctfr IGBT Temp
218
4 Excessive calculated rectifier IGBT junction temperature.
See rectifier Rctfr IGBT Temp (rectifier 19).
Check for proper temperature and flow rate of coolant.
Rctfr IO Board
236
2 Loss of communication to rectifier I/O board.
Rectifier I/O board failure.
1. Clear fault.
2. If fault persists, verify connection between rectifier I/O board and rectifier
control board.
3. If fault still persists, replace rectifier I/O board.
4. If fault still persists, replace rectifier control board.
Rctfr IT Overld
219
4 Short-term current rating of rectifier exceeded.
Low input voltage can result in increased current load. Provide proper input
voltage to the drive.
Rctfr Not Login
238
4 Rectifier took too long to connect to inverter.
1. Check the cabling between the communications interface and the two control
boards.
2. Verify the DPI Data Rate (270) is set to 500K.
3. Connect one DPI device at a time to see if one of the DPI devices is causing the
problem.
4. Replace the communications interface.
5. Replace the rectifier control board.
Rctfr Not OK
232
4 A fault was detected on the rectifier but could not be
displayed on the inverter.
Look at rectifier parameter 243 to see fault code.
Table 21 - Fault Descriptions and Corrective Actions (Frame 3) (Continued)
Fault
No
.
Ty
pe
Description
Action