Technical specifications, Service conditions, Environmental conditions – Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual
Page 233: Appendix a, Service conditions environmental conditions, Appendix
![background image](/manuals/581744/233/background.png)
Rockwell Automation Publication D2-3518-3 - May 2013
233
Appendix
A
Technical Specifications
Service Conditions
Environmental Conditions
AC Line Distribution System Capacity (maximum) for 480V AC Units
Symmetrical fault current capacity: 85,000 A
Short circuit rating if a circuit breaker is used instead of fuses: 65,000 A (optional 100,000 A)
Control Method
Sinusoidal pulse-width-modulated (PWM)
Displacement Power Factor
≥
0.99
Line Frequency
50/60 Hz (
±
2 Hz)
Line Voltage Variation
-10...10%
Motor Lead Lengths
76 m (250 ft) total
Remote Operator Control Wire Length
Up to 1 m (3 ft) from the drive
Analog Speed Reference Resolution
1/4096 (12 bits) 0.025%
Acceleration Adjustment Range
0.1...100.0 seconds (within the ability of current)
Carrier Frequency
2 kHz, 3 kHz, or 4 kHz (software-selectable)
Current Limit Adjustment
25...150% of drive rated amps
Service Factor
1.0
Speed Adjustable Range
From 0 Hz to maximum speed
Speed Regulation
Motor slip dependent
Speed Reference Resolution
0.01 with OIM,
±
32767
counts with a network reference
Assembly Max Air Heat Load
(Heat Dissipated Into Surrounding Air, approx)
LF2 480V AC Input, 405 A output = approx 1800 W
LF2 480V AC Input, 608 A output = approx 2700 W
LF2 480V AC Input, 900 A output = approx 4000 W
LF2 480V AC Input, 1215 A output = approx 5300 W
Max Input Voltage Imbalance
Service factor = 1.0
Condition
Specification
Operating Temperature (inside NEMA/UL Type 1 enclosure)
0...+55 °C (32...131 °F)
Operating Temperature (outside NEMA/UL Type 1 enclosure)
0
...
40
°
C
(
32
...
104
°
F
)
Storage Temperature (ambient)
−
40
...
65
°
C
(−
40
...
149
°
F
)
Humidity
5...95% (non-condensing)