beautypg.com

Figure 67 – Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 147

background image

Rockwell Automation Publication D2-3518-3 - May 2013

147

Chapter 9

Figure 67 - Anlg Out Absolute (341)

Selects the source of the value that drives the user-configurable analog output.

See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a description

of I/O hardware that is present on this drive and is controlled by the inverter.

Sets the user-configurable analog output value when the source value is at
maximum.

See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a description

of I/O hardware that is present on this drive and is controlled by the inverter.

342

Analog Out1 Sel

Range:

0 = Output Freq
1 = Command Freq
2 = Output Amps
3 = Torque Amps
4 = Flux Amps
5 = Output Power
6 = Output Volts
7 = DC Bus Volts
8 = PI Reference
9 = PI Feedback
10 = PI Error
11 = PI Output
12 = %Motor OL
13 = %Drive OL
14 = Application

Default:

14 = Application

Access:

0

Path: Inputs & Outputs > Analog Outputs

See also:

1...7, 12, 135...138, 219, 220

343

Analog Out1 Hi

Range:

4.000...20.000 mA [0.001 mA]
-/+10.000V [0.1V]
0.0...10.000V [0.1V]

Default:

20.0 mA

Access:

0

Path: Inputs & Outputs > Analog Outputs

See also:

31, 342

x

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Analog Out1

Nibble 1

Nibble 2

Nibble 3

Nibble 4