Chapter 9
Figure 67 - Anlg Out Absolute (341)
Selects the source of the value that drives the user-configurable analog output.
AC Line I/O Board Description (Frame 3 Only) on page 25
through
Combined I/O Board Description (Frame 4 Only) on page 29
for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
Sets the user-configurable analog output value when the source value is at
maximum.
AC Line I/O Board Description (Frame 3 Only) on page 25
through
Combined I/O Board Description (Frame 4 Only) on page 29
for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
342
Analog Out1 Sel
Range:
0 = Output Freq
1 = Command Freq
2 = Output Amps
3 = Torque Amps
4 = Flux Amps
5 = Output Power
6 = Output Volts
7 = DC Bus Volts
8 = PI Reference
9 = PI Feedback
10 = PI Error
11 = PI Output
12 = %Motor OL
13 = %Drive OL
14 = Application
Default:
14 = Application
Access:
0
Path: Inputs & Outputs > Analog Outputs
See also:
1...7, 12, 135...138, 219, 220
343
Analog Out1 Hi
Range:
4.000...20.000 mA [0.001 mA]
-/+10.000V [0.1V]
0.0...10.000V [0.1V]
Default:
20.0 mA
Access:
0
Path: Inputs & Outputs > Analog Outputs
See also:
31, 342