A rectifier IOC condition is considered to be redirectable if it occurs more than
1 minute after the rectifier starts running. Any rectifier IOC condition occurring
within 1 minute of a rectifier start is always reported as a rectifier IOC fault; it is
assumed that these faults are caused by conditions within the drive and not by
events on the AC line.
The number of redirects allowed and the amount of time allowed for them before
the redirection is discontinued are controlled by rectifier parameters 300 and
301. The default parameters are five redirects allowed in 24 hours.
Once redirection has been discontinued, it remains discontinued until the drive
is power cycled or until a time equal to the value of IOC Redir Time (300) has
gone by since the last redirectable event.
•
Redirection can be turned off (disabled) by setting IOC Redir Max (301)
to 0.
•
Redirection can be turned on (enabled) by setting IOC Redir Time (300)
to 0 and IOC Redir Max (301) to a nonzero value.
Number of rectifier Instantaneous Overcurrent (IOC) events that can occur
before IOC fault redirection is disabled.
See rectifier parameter 300 for a description of the rectifier IOC fault redirect
facility.
This parameter is for use by service personnel only.
This parameter is for use by service personnel only.
301
IOC Redir Max
Range:
0...30
Default:
5
Access:
0
Path: Communications > In Data Links
See also:
300
302
Service 302
Range:
0...32767
Default:
1000
Access:
0
Path: Communications > In Data Links
See also:
303
Service 303
Range:
0...32767
Default:
N/A
Access:
0
Path: Communications > In Data Links
See also: