No-load Test

Chapter 4

3.

Press

, and press

in the Start Drive? dialog box to

confirm operation.

4.

Observe the direction of motor rotation.

If motor rotating direction is incorrect:

a. Press .

b. Open the Input Circuit Breaker.
c. Perform the Lockout and Tagout procedures.
d. Verify that medium voltage is not present in the drive and in the

motor’s cable connection box by using a hot stick.

e. Swap any two cables in the motor’s cable connection box.
f. Repeat

Close Input Circuit Breaker on page 75

.

If the motor rotating direction is correct, continue to step 5.

IMPORTANT

When the drive is

0.5 Hz, the “Connect” light will be illuminated. When the

speed of the drive surpasses 0.5 Hz, the “Connect” and “Running” lights will be
red.