Chapter
2
Preparation and Inspection
Gather Required Tools and
Test Equipment
Hand Tools
•
Metric wrenches and sockets
•
Torque wrench
•
Assortment of screw drivers
•
Wire stripper/cutter
Electrical Equipment
•
High voltage gloves – 17 kV insulation rating (minimum)
•
Anti-static strap
•
Live-line tool (Hot stick)
•
5 kV Insulation Tester
Test Equipment
•
600V (1000V rating) digital multimeter with assorted clip leads
Computer Requirements and Software
•
Laptop computer
•
USB cable
•
PLC program
•
CCW software
Lockout and Tagout
SHOCK HAZARD: Servicing energized industrial control equipment can be
dangerous. Severe injury or death can result from electrical shock, burn, or
unintended actuation of control equipment. Hazardous voltages may exist in
the cabinet even with the input circuit breaker in the off position. Required
practice is to disconnect and lock out control equipment from power sources,
and confirm discharge of stored energy in capacitors. If it is necessary to work in
the vicinity of energized equipment, the safety related work practices outlined
in Electrical Safety requirements for Employee Work places must be followed.
Before attempting any work, verify the system has been locked out and tested
to have no potential.