Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

37

Commissioning

Chapter 3

The Select Local Control? dialog box appears.

5.

Select

to confirm Local Control, and press

to

return to the Main Interface Screen.

Set P Parameters to Enable Testing

There are two specific “P” parameters that must be changed to allow the Control
System Check to proceed.

This section is password protected and the setup login process must be
completed before making any changes.

Access Setup Settings

1.

Press

from the Main Interface Screen.

2.

Press

under

Parameter Access Level

.