Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

Chapter 4

No-load Test

Energize Drive Control Circuit

The “Energize Control Circuit” process is already described on

page 32

. For the

“Energize Drive Control Circuit” procedure, repeat the process in the same
sequence, without the requirements of taking voltage measurements.

1.

Close circuit breaker Q1.

2.

Start UPS. Press and hold the ON button for approximately 3 seconds.

3.

Close circuit breakers Q2, Q3, Q5, and Q6 in the LV Control Panel.

4.

Close circuit breakers Q4 and Q7 in the Isolation Transformer Cabinet LV
Panel.

Configure P and T Parameters

Set the P parameters and T parameters as shown in

Table 12

.

This table outlines the specific parameters that must be checked and/or
modified. Parameters that must be modified are outlined in the Instruction
column. All other parameters listed must be verified. For special functions or
actions which are not listed here, but are commonly performed while
commissioning a drive, see

Special Function Parameter Settings on page 87

.

TIP

See

Set P Parameters to Enable Testing on page 37

for information on how to

access and change parameters.

Table 12 - Setup and R&D Parameters

P
Parameter

Description

Default

Modify
Root

(1)

Min.
Value

Max.
Value

Login
Level

Instruction

P004

Command Source
0: Communication Port
1: Other Sources

0

OFF

0

1

Setup

P007

Number Of Power Cells Per Phase

9

ON

0

9

Setup

Set to 0 for Control System Check. Afterwards, set to actual value
according to Electrical Drawings

P008

Motor Rotation Direction Under Local Control
1: Forward
0: Reverse

1

OFF

0

1

Setup

P009

Motor Rotation Direction Command
Selection
0: Local
1: DCS

0

OFF

0

1

Setup

P024

Stop Method
0: Ramp Down
1: Coast Stop

0

ON

0

1

R&D

P040

Safe Start Condition
0: Zero Frequency Command Required
1: Frequency Command Allowed

1

OFF

0

1

Setup

P089

Skip Frequency Enable
0: Disable
1: Enable

0

ON

0

1

R&D

P090

Skip Frequency 1 Lower Limit

0

ON

0

75

R&D