Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Commissioning Manual User Manual

Page 55

background image

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

55

Commissioning

Chapter 3

3.

Close the customer-supplied input circuit breaker by installing a
temporary jumper wire (X-117, X-119).

Verify the input circuit breaker is closed.

Verify Operation of Input/Output and Bypass Contactors
(Automatic Bypass)

Input/Output Drive Contactors

1.

Press

from the Main Interface screen.

IMPORTANT

Turn the 3-position on the selector switch on the front of the LV Cabinet to the
Drive position.