beautypg.com

Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Commissioning Manual User Manual

Page 69

background image

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

69

No-load Test

Chapter 4

P091

Skip Frequency 1 Upper Limit

0

ON

0

75

R&D

P092

Skip Frequency 2 Lower Limit

0

ON

0

75

R&D

P093

Skip Frequency 2 Upper Limit

0

ON

0

75

R&D

P113

Flying Start-Initial Output Voltage
Percentage (%)

5

ON

0

100

R&D

P114

Flying Start-Current Comparison Delay For
Motor Speed Search (ms)

1000

ON

0

5000

R&D

P115

Flying Start-Current Threshold For Successful
Motor Speed Search

5

ON

0

100

R&D

P198

HECS Rated Current (A)

0

ON

0

5000

Setup

Set value according to the Electrical Drawings

P199

Motor Rated Current (A)

0

ON

0

5000

Setup

Set value according to the customer motor nameplate data

P205

Motor Uab Voltage Scaling Factor Correction

199.99

ON

0

199.99

R&D

P206

Motor Uac Voltage Scaling Factor Correction

199.99

ON

0

199.99

R&D

P213

Output Short-Circuit Fault Threshold

180

ON

0

199.99

Setup

P216

High-Frequency Output Over Current
Threshold

120

ON

0

199.99

Setup

P224

Output Voltage Deviation Fault Threshold

80

ON

0

199.99

Setup

Set to 120 for Control System Check. Set to 80 afterwards

P252

Motor In Stopping Condition Threshold

1

ON

0

100

R&D

P253

Motor Coast Stop Time

10

ON

0

10000

R&D

P259

Frequency Command Analog Offset

0

ON

-100

199.99

R&D

P260

Frequency Command Analog Scaling Factor

100

ON

0

199.99

Setup

P262

Frequency Command Source Selection
0: Digital
1: Analog

0

OFF

0

1

Setup

P335

Analog Output #1 Scaling Factor

100

ON

0

199.99

Setup

DCS display the output voltage proportion coefficient and can be
changed as the customer operation request from 0...200%

(2)

P339

Analog Output #2 Scaling Factor

100

ON

0

199.99

Setup

DCS display the output current proportion coefficient and can be
changed as the customer operation request from 0...200%

(2)

P352

Rated Frequency HMI Display Integer Part

50

ON

0

75

Setup

P355

Motor Voltage HMI Display Integer Part

10000

ON

0

16384

Setup

Local display voltage correction coefficient, the value must be
done according to the rating of the inverter output voltage
setting.
For example: if the output is 3 kV, then set P355 = 3000

P358

Actual Frequency HMI Display Integer Part

50

ON

0

75

Setup

P361

Motor Current HMI Display Integer Part

0

ON

0

5000

Setup

Normally P361 = P199

P399

Deceleration Time (s)

300

ON

0

3276

Setup

Default value is 300 s. Set according to customer specification
The time from 50...0 Hz after stopping the motor

P401

Acceleration Time (s)

200

ON

0

3276

Setup

Default value is 200 s. Set according to customer specification
The time from 0...50 Hz after starting the motor

P413

Frequency Command Lower Limit

0

ON

-16384

16384

R&D

P414

Frequency Command Deadband Upper Limit

0.49

ON

0

100

R&D

P415

Frequency Command Upper Limit

16384

ON

-16384

16384

R&D

Table 12 - Setup and R&D Parameters (Continued)

P
Parameter

Description

Default

Modify
Root

(1)

Min.
Value

Max.
Value

Login
Level

Instruction