Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

Chapter 3

Commissioning

6.

Under Control Owner Selection, press

.

7.

Select

to confirm selection in the Select Local Control?

dialog, and press

to return to the Main Interface Screen and

confirm the Local status indicator is on.

Verify Operation of Input/Output and Bypass Isolation Switches
(Manual Bypass)

Input/Output Isolation Switches

1.

Press

from the Main Interface screen.