72

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

Chapter 4

No-load Test

2.

In the Switch Method Selection dialog, press

or

.

3.

If you select

, the:

drive must be set to Local Control

position switch must be set to Drive

bypass contactor must be ON

drive must not be running.

4.

If you select

, the:

drive must be set to Local Control

position switch must be set to Drive

drive must be running.

5.

Press

to confirm selection.

ATTENTION: If the conditions are incorrect, the following dialog appears.