44

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

Chapter 3

Commissioning

2.

Press

to accept and begin the simulation.

Actual Frequency:

will show the frequency increasing to 50 Hz.

3.

Once the actual frequency has reached the set frequency, press

and press

in the Stop Drive? dialog to confirm

action.

The actual frequency will decrease to 0 Hz.