Commissioning

Chapter 3

6.

Press

to remove the fault. Press

to confirm

operation in the Reset Drive? dialog.

Verify Switching from Local Control to Remote Control

Depending on whether the drive has an automatic or manual Bypass or no Bypass
configuration, the Operation Interface screen will be different.

1.

Press

from the Main Interface Screen.

2.

Press

in

the

Control Owner Selection

.

3.

Press

in the Select Remote Control? dialog.

4.

Press

to return to the Main Interface Screen and confirm

Remote

status indicator light is on.

5.

Press

from the Main Interface Screen.