Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

Chapter 3

Commissioning

Set Date and Time Zone

To access the Date and Time Zone settings, you must exit the PowerFlex 6000
HMI to Windows CE.

Access T Parameters

1.

Press

from the Main Interface Screen.

2.

Press

under

Parameter Access Level.

The Setup Login dialog box appears. Press

.

3.

Enter the User and Password details.

4.

Press

to

login.

5.

Once logged in, press

.

6.

Press

in the Setup Parameter Type.

7.

Press the T10 parameter input field. Enter “555” and press

.

8.

Press

and

to confirm.

TIP

It will take 3...5 minutes to shutdown.