Chapter 3

Commissioning

3.

Press

to view alarm record.

.

4.

Remove the jumper wires to remove the warning.

Simulate Transformer Overtemperature Trip

1.

Open the LV door of the Isolation Transformer cabinet.

2.

Using a jumper wire, connect terminal blocks 401 and 418 on the
transformer protection relay.

3.

Press

to view the alarm record.

4.

Remove the jumper wires to remove the Trip message.

5.

Press

to return to the Main Interface Screen.