Chapter 4

No-load Test

Change Parameter T13:

1.

Press the T13 Parameter input field.

2.

Enter desired speed values in the Enter Four Steps dialog box.

Press the input field to enter a value.

3.

Press

to

accept.

IMPORTANT

Parameter T08 must be set to 2.

IMPORTANT

Refer to publication 6012-UM001_-EN-P, PowerFlex 6000 Drive Bypass Units
User Manual or detailed information about operating the switches in bypass
cabinets.