Verify e-stop functionality – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Commissioning Manual User Manual

Page 50

background image

50

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014

Chapter 3

Commissioning

5.

Press

to return to the Main Interface Screen.

6.

Press

to remove the fault. Press

to confirm

operation in the Reset Drive? dialog.

Verify E-Stop Functionality

1.

Press

on the Main Interface Screen to start the drive.

2.

Push the E-stop button on the front of the LV Control cabinet.

3.

Press

and confirm the E-stop Trip fault.

4.

Twist to pull out the E-stop button on the front of the LV Control cabinet.

5.

Press

to return to the Main Interface Screen.