Commissioning

Chapter 3

Verify Operation of DCS Input and Output Signals

Figure 17 - Status Indicators

Table 9 - Drive to DCS

Signal Name

Terminal Number

HMI Status

Terminal Open

Terminal Closed

MVPRE-Closed CB

901-902

Allowed

Red

Grey

MV CLOSING

903-904

MVClosd

Red

Grey

Warning

905-906

Warning

Red

Grey

Fault

907-908

Warning

Red

Grey

Drive running

909-910

Running/Connect

Red

Grey

Drive STOP

911-912

Running/Connect

Red

Grey

READY

913-914

Ready

Red

Grey

DCS control

915-916

Remote

Red

Grey

Local

Grey

Red

Table 10 - 4-20 mA

Output Current

925-926

Motor Current

0-Rated Current

Output Frequency

927-928

Actual Frequency

0-Rated Frequency