Armorstratix 5700 switch installation, Installation guidelines – Rockwell Automation 1783-BMxxx Stratix 5700 Ethernet Managed Switches User Manual User Manual
Page 57
Rockwell Automation Publication 1783-UM004E-EN-P - June 2014
57
Switch Installation Chapter 2
ArmorStratix 5700 Switch
Installation
Installation Guidelines
ATTENTION: Environment and Enclosure
This equipment is intended for use in overvoltage Category II applications (as
defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not
provide adequate protection to radio communication services in such
environments.
This equipment is supplied as enclosed equipment. It should not require additional
system enclosure when used in locations consistent with the enclosure type ratings
stated in the Specifications section of this publication. Subsequent sections of this
publication may contain additional information regarding specific enclosure type
ratings, beyond what this product provides, that are required to comply with
certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publica
for additional installation requirements
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the
degrees of protection provided by enclosures
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
ATTENTION: Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP enclosure type
requirements.
ATTENTION: The console ports are intended for temporary local programming
purposes only and not intended for permanent connection.
The console port cables are not to exceed 3.0 m (9.84 ft) and must not contain
hubs.