Dashboard overview, Front panel and status indicators – Rockwell Automation 1783-BMxxx Stratix 5700 Ethernet Managed Switches User Manual User Manual
Page 119
Rockwell Automation Publication 1783-UM004E-EN-P - June 2014
119
Manage the Switch via the Device Manager Web Interface Chapter 4
Dashboard Overview
You can use the dashboard to monitor switch status and performance.
The Dashboard window is similar to the Monitor > Trends window. The
Dashboard window displays the instantaneous status while the Trends window
displays the historical status. By using them together, you can gather the detailed
conditions of the switch and its ports. For information about the Trends window,
see
Front Panel and Status Indicators
The Front Panel view is a graphical display of the switch front panels.
The switch components on the front panel view are color-coded by status. The
colors help you to quickly see if a fault or an error condition exists. The
system-level status indicators and port-level status indicators shown on the front
panel view match those on the physical switch.
Table 9 - Front Panel Status Indicators
Indicator
Status
Description
EIP Mod
The EIP Mod status indicator shows the status of the switch.
Off
Power to the switch is off or is not properly connected.
Solid green
The switch is operating properly.
Blinking green
The switch is not configured (for example, the switch does not have an IP address configured).
Blinking red
The switch has detected a recoverable system fault.
Solid red
The switch has detected a non-recoverable system fault.
Blinking green and red
The switch is running its power-on self-test (POST).
DC_A
DC_B
Off
Power to the switch is off or is not properly connected.
Solid green
Power is present on the associated circuit.
Solid red
Power is not present on the associated circuit, and the switch is configured for dual-input power.
Alarm Out
Off
Alarm Out not configured, or the switch is off.
Solid green
Alarm Out is configured; no alarm is detected.
Blinking red
The switch has detected a major alarm.