beautypg.com

Rockwell Automation 1783-BMxxx Stratix 5700 Ethernet Managed Switches User Manual User Manual

Page 244

background image

244

Rockwell Automation Publication 1783-UM004E-EN-P - June 2014

Appendix A Module-defined Data Types

In the Logix Designer application, predefined tags for Input and Output data
types have a structure corresponding to the switch selected when it was added to
the I/O tree. Its members are named in accordance with the port names.

You can disable a switch port by setting the corresponding bit in the output tag.
The output bits are applied every time the switch receives the output data from
the controller when the controller is in Run mode. When the controller is in
Program mode, the output bits are not applied.

The port is enabled if the corresponding output bit is 0. If you enable or disable a
port by using the Device Manager Web interface or the CLI, the port setting can
be overridden by the output bits the next time they are applied. The output bits
always take precedence, regardless of whether the Device Manager Web interface
or CLI was used to enable or disable the port.

The tables in this appendix list module-defined data types for Stratix 5700
switches. The tables include information for input (as indicated by an I) and
output (as indicated by an O).