In-t, Amov – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 92

Publication 900-UM007D-EN-E - January 2011
3-22
Configuration & Basic Operation
Control Output (Cooling); Auxiliary Output 1: Alarm 1; Auxiliary Output 2:
Alarm 2
1.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 3.29
2.
Select the Standard or Heating/Cooling Control Mode parameter by
pressing the
M key.
Figure 3.30
Figure 3.31
3.
Press the
U key to set the parameter to h-c (Heating/Cooling)
Control Mode.
Note:
The following output assignments do not need to be set because
they are set automatically as defaults by changing the control mode, but
they are shown here as a reference for checking the assignments for each
output.
Figure 3.32
4.
Select the Move to Advanced Setting function group parameter by
pressing the
M key.
5.
Press the
D key to enter the password (−169), and move from the
Initial Setting function group to the Advanced Setting function group.
Figure 3.33
C
25
100
PV/SP
in-t
5
Input type
5-hc
stnd
Standard or
heating/cooling
5-hc
h-c
amov
0
Move to Advanced
Setting Function Group