Parameter Functions & Definitions
5-97
Function:
This parameter allows you to configure the units of time used for
the soak time when the simple program function is used.
Related Parameters
• Program Start, Soak Time Remain (Operation function group, page
5-15)
• Soak Time, Wait Band (Adjustment function group, page 5-40)
• Program Pattern (Initial Setting function group, page 5-57)
Alarm SP Selection
Conditions of Use:
Alarm 1, 2, and 3 functions must be assigned. The SP
Ramp Set Value must NOT be set to OFF. The ST parameter must be set to
OFF. The Alarm Type parameter must set to 1, 2, 3, 4, 5, 6, or 7.
Function:
This parameter allows you to configure whether the set point that
triggers a deviation alarm during SP ramp operation is the ramp SP or target
SP.
Related Parameters
• SP Ramp Set Value (Adjustment function group, page 5-41)
• ST (Initial Setting function group, page 5-56)
Manual MV Limit Enable
Conditions of Use:
The control must be set to 2-PID control.
Table 5.DQ
Selections
Default
m: Minutes, h: Hours
m
Selections
Default
sp-m: Ramp SP, sp: SP
sp-m
alsp
manl