L.adj, Lcr1 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 129

Publication 900-UM007D-EN-E - January 2011
Configuration & Basic Operation
3-59
HS Alarm Settings
1.
Press the
O
key for at least 1 second to move from the Advanced
Setting function group to the Initial Setting function group and then to
the Operation function group.
Figure 3.120
2.
Press the
O
key for less than 1 second to move from the Operation
function group to the Adjustment function group.
Figure 3.121
3.
Select the Leakage Current 1 Monitor parameter by pressing the
M key.
Check the current value. Next, set the HS Alarm 1 parameter.
Figure 3.122
4.
Select the HS Alarm 1 parameter by pressing the
M key. Refer to How to
Calculate Heater Current Detection Values
when setting the values.
Figure 3.123
5.
For this example, set 2.5. To return to the Operation function group,
press the
O
key for less than 1 second.
Figure 3.124
C
25
100
PV/SP
l.adj
Adjustment
function
group display
lcr1
0.0
Leakage current
1 monitor
hs1
50.0
HS alarm 1
hs1
2.5