The following table shows the relationship between the Multi-SP Uses
parameter value and the selected set point.
Note: The set point can also be switched using PC communications. This is
supported by 900-TC8, 900-TC16, and 900-TC32.
Multi-SP Setup
EXAMPLE
Operation Procedure: To Select Set Points (0/1/2/3)
The following example configures the Number of Multi-SP Uses parameter to
2 (Multi-SP, 4 points). Refer to Table 4.I.
Before you configure the Number of Multi-SP Uses parameter, you must first
cancel protection from the Advanced Setting function group. For additional
details on how to cancel key protection, refer to page 4-33, Using the Key Protect
Function Group
.
1. Press the
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.33
Table 4.I
Multi-SP Uses Parameter Value
Selected Set Point
0
Select Set Point 0 value
1
Select Set Point 1 value
2
Select Set Point 2 value
3
Select Set Point 3 value