Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 370

Publication 900-UM007D-EN-E - January 2011
B-10
Cold Junction
Compensation Method
cjc
OFF, ON
off on
ON
None
MB Command Logic
Switching
rlrv
OFF, ON
off on
OFF
None
PV Color Change
colr
Orange, Red, Green
Red to Green: When ALM1 is lit
Green to Red: When ALM1 is lit
Red to Green to Red
Within PV stable band: Green
Outside stable band: Red
Green to Orange to Red
Within PV stable band: Green
Outside stable band: Green, Red
Orange to Green to Red
Within PV stable band: Green
Outside stable band: Green, Red
org
red
grn
r-g
g-r
r-g.r
g-o.r
o-g.r
RED
None
PV Stable Band
pv-b
Universal input: 0.1…999.9
5.0
°C or °F ➊
Analog input: 0.01…99.99
5.00
%FS
Alarm 1 ON Delay
a1on
0…999 (0: ON Delay disabled)
0
Second
Alarm 2 ON Delay
a2on
0…999 (0: ON Delay disabled)
0
Second
Alarm 3 ON Delay
a3on
0…999 (0: ON Delay disabled)
0
Second
Alarm 1 OFF Delay
a1of
0…999 (0: OFF Delay disabled)
0
Second
Alarm 2 OFF Delay
a2of
0…999 (0: OFF Delay disabled)
0
Second
Alarm 3 OFF Delay
a3of
0…999 (0: OFF Delay disabled)
0
Second
Input Shift Type
istp
INS1:
Temperature input
1-point shift
INS2:
Temperature input
2-point shift
ins1
ins2
INS1
None
MV at Stop and Error
Addition
mvst
OFF, ON
off on
OFF
None
Auto/Manual Select
Addition
amad
OFF, ON
off on
OFF
None
RT
rt
OFF, ON
off on
OFF
None
HS Alarm Use
hsu
OFF, ON
off on
ON
None
HS Alarm Latch
hsl
OFF, ON
off on
OFF
None
HS Alarm Hysteresis
hsh
0.1…50.0
0.1
A
Table B.F — Advanced Setting Function Group
Parameters
Characters
Setting (Monitor) Value
Display
Default
Unit
Set Value