Parameter Functions & Definitions
5-51
• If a platinum resistance thermometer (RTD) is mistakenly connected
while a setting for other than a platinum resistance thermometer is in
effect, the controller error code S.ERR will be displayed. To clear the
S.ERR display, check the wiring and then cycle the controller power.
Table 5.BD — Global Temperature (GT) Input Type Controllers
Input Type
Specifications
Set Value
Input Temperature Range
Controller
Type with
Thermocouple
and
Resistance
Thermometer
(RTD) inputs
Platinum resistance
thermometer (RTD)
Pt100
0
−200…850 (°C)/−300…1,500 (°F)
1
−199.9…500.0 (°C)/−199.9…900.0 (°F)
2
0.0…100.0 (
°C)/0.0…210.0 (°F)
JPt100
3
−199.9…500.0 (°C)/−199.9…900.0 (°F)
4
0.0…100.0 (
°C)/0.0…210.0 (°F)
Thermocouple
K
5
−200…1,300 (°C)/−300…2,300 (°F)
6
−20.0…500.0 (°C)/0.0…900.0 (°F)
J
7
−100…850 (°C)/−100…1,500 (°F)
8
−20.0…400.0 (°C)/0.0…750.0 (°F)
T
9
−200…400 (°C)/−300…700 (°F)
10
−199.9…400.0 (°C)/−199.9…700.0 (°F)
E
11
-200…600 (
°C)/-300…1,100 (°F)
L
12
−100…850 (°C)/−100…1,500 (°F)
U
13
−200…400 (°C)/−300…700 (°F)
14
−199.9…400.0 (°C)/−199.9…700.0 (°F)
N
15
−200…1,300 (°C)/−300…2,300 (°F)
R
16
0…1,700 (
°C)/0…3,000 (°F)
S
17
0…1,700 (
°C)/0…3,000 (°F)
B
18
100…1,800 (
°C)/300…3,200 (°F)
Infrared Temperature
Sensor
ES1B
10…70 (
°C)
19
0…90 (
°C)/0…190 (°F)
60…120 (
°C)
20
0…120 (
°C)/0…240 (°F)
115…165 (
°C)
21
0…165 (
°C)/0…320 (°F)
140...260 (
°C)
22
0…260 (
°C)/0…500 (°F)
Millivolt input
0…50 mV
23
One of the following ranges depending on the scaling.
−1,999…9,999
−199.9…999.9
Thermocouple
W
24
0…2,000 (
°C)/0…3,200 (°F)
PLII
25
0…1,300 (
°C)/0…2,300 (°F)
Note:
Shaded box indicates default selection for the GT controller type.