C700, C400 4, Bias – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 386

Publication 900-UM007D-EN-E -January 2011
C-8
Calibration
value is outside the specified range, the Number 2 display will flash and
the count value will NOT be temporarily registered.
6. Press the M key to set the Bulletin 900 Controller to the state below. Set
STV to –6 mV. Allow the count value on the No. 2 display to fully
stabilize, then press the
D key to temporarily register the calibration
setup. If the count value is outside the specified range, the Number 2
display will flash and the count value will NOT be temporarily
registered.
Figure C.9
7. Press the M Key. The display changes as shown above.. Set the STV to
700 mV.
Allow the count value on the No. 2 display to fully stabilize, then press
the
D Key to temporarily register the calibration settings. If this count
value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
Figure C.10
8. Press the M Key. The display changes as shown on the left.Set the STV
to 400 mV. Allow the count value on the No. 2 display to fully stabilize,
then press the
D Key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered
Figure C.11
9. When the M Key is pressed, the status changes as shown to the left.
Figure C.12
t
-
-6
2988
c700
-
ba13
c400
4
29be
bias
35b8