Checking indication accuracy – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 396

Publication 900-UM007D-EN-E -January 2011
C-18
Calibration
Checking Indication
Accuracy
• After calibrating input, make sure to check indication accuracy to make
sure that the Bulletin 900 Controller has been correctly calibrated.
• Operate the Bulletin 900 Controller in the PV/SP monitor mode.
• Check the indication accuracy at the Upper- and Lower-Limits and
mid-point.
Checking Accuracy of a Thermocouple or Non-Contact
Temperature Sensor
• Preparation: The following figure shows the required device
connection. Make sure that the Bulletin 900 Controller and cold
junction compensator are connected by a compensating conductor for
the thermocouple that is to be used during actual operation. For the
non-contact temperature sensor, connect a K thermocouple, and
configured the Input Type to the K thermocouple.
Figure C.36
Cold Junction Compensator
Input Power Supply
Compensation Conductor
900-TC8
1
2
19
20
-
+
STV
Cold Junction Compensator
Input Power Supply
Compensation Conductor
900-TC16
9
10
4
5
-
+
STV
Cold Junction Compensator
Input Power Supply
Compensation Conductor
900-TC32
1
2
11
12
-
+
STV
900-TC8
900-TC16
900-TC32