P280, P390, P200 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 391: P140
Publication 900-UM007D-EN-E - January 2011
Calibration
C-13
Figure C.22
5. Press the M key to display the count value for each Input Type. The
No. 2 display at this time displays the currently entered count value in
Hexadecimal. Set the 6-dial as follows:
• Input Type 0: 390 Ω
• Input Type 1, 2, 3 or 4: 280 Ω
Figure C.23
6. Allow the count value on the No. 2 display to fully stabilize, then press
the
D key to temporarily register the calibration setup. If this count
value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
7. Press the M Key to display the count value for each input type. The No.
2 display at this time shows the currently entered count value in
hexadecimal.Set the 6-dial as follows:
• Input type 0: 200 Ω
• Input type 1, 2, 3 or 4: 140 Ω
Figure C.24
8. Allow the count value on the No. 2 display to fully stabilize, then press
the
D key to temporarily register the calibration setup.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
When the
M key is pressed, the status changes as shown in Figure
C.25. Set the 6-dial to 10
Ω.
9. Allow the count value on the No. 2 display to fully stabilize, then press
the
D Key to temporarily register the calibration settings.If this count
value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
adj
30
p280
e26b
Input Type
1, 2, 3, 4:
p390
e20c
Input Type
0:
p200
93a7
p140
e26b