Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 186
Publication 900-UM007D-EN-E - January 2011
4-50
Parameter Adjustments & Application Considerations
Determining the LBA Detection Time
To manually configure the LBA detection time, configured the LBA Detection
Time parameter to twice the LBA reference time given in the example below.
EXAMPLE
Procedure
1. Set the output to the maximum value.
2. Measure the time required for the change in the input to reach the LBA
band.
Figure 4.95
3. Set the LBA Detection Time parameter to two times the measured time.
LBA Level
Configure the control deviation when the control loop is working properly.
The default is 8.0 (
°C/°F) for Controllers with Thermocouple/Resistance
Thermometer Multi-Inputs and 10.00% FS for Controllers with Analog
Inputs.
LBA Band
There is assumed to be an error in the control loop if the control deviation is
greater than the threshold configured for the LBA Level parameter and if the
control deviation does not change by at least the value configured for the LBA
Band parameter.
The default is 3.0 (
°C/°F) for Controllers with Thermocouple/Resistance
Thermometer Multi-Inputs and 0.20% FS for Controllers with Analog Inputs.
MV = 100%
PV
Temperature
Time
Measurement time
Tm
LBA band
LBA detection time = Tm
Ч
2