1v - 5, 2v10, 1v - 1 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 395: 2v - 1

Publication 900-UM007D-EN-E - January 2011
Calibration
C-17
Figure C.33
6. When the M key is pressed, the status changes as shown in the figure
below.
Set the STV to 1V.
Allow the count value on the No. 2 display to fully stabilize, then press
the
D key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
Figure C.34
7. When the M key is pressed, the status changes as shown in the figure
below.
The data to be temporarily registered is not displayed if it is not
complete.
Press the
U key. The No. 2 display changes to yes. Release the key and
wait 2 seconds or press the
M key. This stores the temporarily
registered calibration data to EEPROM.
To cancel the saving of temporarily registered calibration data to
EEPROM, press the
M key (while no is displayed in the No. 2 display)
without pressing the
U key.
Figure C.35
8. The calibration mode is ended by turning the power OFF.
1v
-
5
c7c3
Input Type
2 or 3:
2v10
b104
Input Type 4:
1v
-
1
5ac0
Input Type
2 or 3:
2v
-
1
4ad9
Input Type
4:
str
no