beautypg.com

Spdp odsl, Pv/sp display screen selection, Mv display selection – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 331

background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-103

PV/SP Display Screen Selection

Conditions of Use:

The No. 3 display must be supported (900-TC8)

Function:

This parameter allows you to configure what will be displayed on

the PV/SP Screen No. display and the order of the display. The default is 4.

Note:

A 2- level display is set at the time of shipping from the factory (set
value = 0). A 3- level display is activated if parameters are initialized (set
value =4).

Related Parameter

• Process Value Set Point (Operation function group, page 5-8)
• MV Display Selection (Advanced Setting function group, page 5-103)

MV Display Selection

Conditions of Use:

The No. 3 display must be supported(900-TC-8). Heating

and cooling control must be used. The PV/SP Display Screen Selection
parameter must be set to 1, 2, 4, or 6, or the Monitor/Setting Item 1 to 5
parameter must be set to 2.

Table 5.DZ

Set Value

Display Contents

0

Only PV/SP is displayed (with no No. 3 display).

1

PV/SP/Multi-SP and PV/SP/MV are displayed in order

2

PV/SP/MV and PV/SP/Multi-SP are displayed in order

3

Only PV/SP/Multi-SP is displayed.

4

PV/SP/MV is displayed

5

PV/SP/Multi-SP and PV/SP/Soak time remain are displayed in order

6

PV/SP/MV and PV/SP/Soak time remain are displayed in order

7

Only PV/SP/Soak time remain is displayed.

➊ The MV for heating and cooling control is configured in the MV Display Selection parameter.

spdp

odsl