Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 363

Publication 900-UM007D-EN-E - January 2011
B-3
➊ Set NONE as the unit for controllers with 0…50 Millivolt Inputs.
Table B.B — Adjustment Function Group
Parameters
Characters Setting (Monitor) Value
Display
Default
Unit
Set
Value
Dead Band
c-db
Universal input:
−199.9…999.9
0.0
°C or °F ➊
Analog input:
−19.99…99.99
0.00
%FS
Manual Reset Value
of-r
0.0…100.0
50.0
%
Hysteresis (heating)
hys
Universal input: 0.1…999.9
1.0
°C or °F ➊
Analog input: 0.01…99.99
0.10
%FS
Hysteresis (cooling)
chys
Universal input: 0.1…999.9
1.0
°C or °F ➊
Analog input: 0.01…99.99
0.10
%FS
Soak Time
soak
1…9,999
1
min or h
Wait Band
wt-b
Universal input: OFF, 0.1…999.9
off
0.1 to
999.9
OFF
°C or °F ➊
Analog input: OFF, 0.01…99.99
off
0.01 to
99.99
OFF
%FS
MV at Stop
mv-s
−5.0…105.0 (standard)
−105.0…105.0 (heating/cooling)
0.0
%
MV at PV Error
mv-e
−5.0…105.0 (standard)
−105.0…105.0 (heating/cooling)
0.0
%
SP Ramp Set Value
sprt
OFF or 1…9,999
off
1 to 9999
OFF
EU/s,
EU/min
MV Upper-Limit
ol-h
MV Lower-Limit +0.1 /105.0 (standard)
0.0…105.0 (heating/cooling)
105.0
%
MV Lower-Limit
ol-l
−5.0 to MV Upper-Limit −0.1 (standard)
−105.0…0.0 (heating/cooling)
−5.0 (standard)
−105.0 (heating/
cooling)
%
MV Change Rate
Limit
orl
0.0...100.0 (0.0: MV Change Rate Limit
Disabled)
0.0
%/s
Extraction of Square
Root Low-cut Point
sqrp
0.0...100.0
0.0
%