Sub2 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 322

Publication 900-UM007D-EN-E - January 2011
5-94
Parameter Functions & Definitions
Related Parameter
• Program Pattern (Initial Setting function group, page 5-57)
Auxiliary Output 2 Assignment
(900-TC8, 900-TC16)
Conditions of Use:
Auxiliary Output 2 must be assigned.
Function:
This parameter allows you to configure the function assigned to
Auxiliary Output 2.
Table 5.DM
Auxiliary Output 1 Function
Default
none:
No function is assigned to auxiliary output 1
alm1 ➌
o:
Heating Control Output is output
c-o:
Cooling Control Output is output
➊➍
alm1:
Alarm 1is output
alm2:
Alarm 2 is output
alm3:
Alarm 3 is output (900-TC8 only)
p.end:
Program end is output
➋
ralm:
Control output ON/OFF count alarm
➌
➊ If c-o is assigned for standard control, a value equivalent to 0% will be output.
➋ Can be selected only when the program pattern is not set to OFF, but the function is disabled.
➌ If a setting is changed when the Program Pattern parameter is not set to OFF, control automatically switches to
p.end.
➍ If the Standard or Heating/Cooling parameter is set to heating/cooling control, this parameter will automatically
be set to
c-6 (900-TC32).
sub2