Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 367

Publication 900-UM007D-EN-E - January 2011
B-7
Table B.C — Initial Setting Function Group
Parameters
Characters
Setting (Monitor) Value
Display
Default
Unit
Set Value
Alarm 2 Type
alt2
Same settings as the alarm 1 type.
NOTE: The 12: LBA (Loop Burnout
Alarm) setting cannot be used.
2
None
Alarm 2 Hysteresis
alh2
Universal input: 0.1…999.9
0.2
°C or °F ➊
Analog input: 0.01…99.99
0.02
%FS
Alarm 3 Type
alt3
Same settings as the alarm 2 type
2
None
Alarm 3 Hysteresis
alh3
Universal input: 0.1…999.9
0.2
°C or °F ➊
Analog input: 0.01…99.99
0.02
%FS
Transfer output type
tr-t
OFF:OFF
SP:Set point
SP-M:Ramp set point
PV:Process value
MV:Manipulated variable (heating)
C-MV:Manipulated variable (cooling)
off
sp
sp-m
pv
mv
c-mv
OFF
None
Transfer Output
Upper-Limit
tr-h
➋
➋
➋
Transfer Output
Lower-Limit
tr-l
➋
➋
➋
Linear Current Output
o1-t
4-20: 4…20 mA
0-20: 0…20 mA
4-20
0-20
4-20
None
Number of Multi-SP
Uses
ev-m
0…2
1
None
Event Input
Assignment 1
ev-1
NONE: None
STOP:
RUN/STOP
MANU: Auto/manual switch
PRST:
Program start
➌
DRS: Invert Direct/Reverse Operation
AT-2: 100% AT Execute/Cancel
AT-1: 40% AT Execute/Cancel
WTPT: Setting Change Enable/Disable
LAT: Alarm Latch Cancel
none
stop
manu
prst
drs
at-2
at-1
wtpt
lat
NONE
None
Event Input
Assignment 2
ev-2
NONE: None
STOP:
RUN/STOP
MANU: Auto/manual switch
PRST:
Program start
➌
DRS: Invert Direct/Reverse Operation
AT-2: 100% AT Execute/Cancel
AT-1: 40% AT Execute/Cancel
WTPT: Setting Change Enable/Disable
LAT: Alarm Latch Cancel
none
stop
manu
prst
drs
at-2
at-1
wtpt
lat
STOP
None