Csel t-u, Character select led, Soak time units – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 324
Publication 900-UM007D-EN-E - January 2011
5-96
Parameter Functions & Definitions
Related Parameters
• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
(Initial Setting function group)
Character Select LED
Function:
This parameter allows you to select the LED display type for your
controller. The following two types of displays are available:
• 11-segment display
• 7-segment display
When set to
on
, an 11-segment display is used.
Soak Time Units
Conditions of Use:
The Program Pattern parameter must NOT be set to
OFF.
Table 5.DO
Auxiliary Output 3 Function
Default
none:
No function is assigned to auxiliary output 3
alm3 ➌
o:
Heating Control Output is output
c-o:
Cooling Control Output is output
➊
alm1:
Alarm 1is output
alm2:
Alarm 2 is output
alm3:
Alarm 3 is output
p.end:
Program end is output
➋
ralm:
Control output ON/OFF count alarm
➋
➊ If
c-o
is assigned for standard control, a value equivalent to 0% will be output.
➋ Can be selected only when the program pattern is not set to OFF, but the function is disabled.
➌ If the Standard or Heating/Cooling parameter is set to heating/cooling control when there is no Control Output
2 (900-TC8), control automatically switches to
c-o
.
Table 5.DP
Selections
Default
on: 11-segment display, off: 7-segment display
on
csel
t-u