Amov, Init, In-t – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 225
Publication 900-UM007D-EN-E - January 2011
Parameter Adjustments & Application Considerations
4-89
2. Select the Move to Advanced Setting function group parameter by
pressing the
M Key.
Figure 4.202
3. Use the D Key to enter the password (“-169”). It is possible to move to
the Advanced Setting function group by either pressing the
M Key or
waiting two seconds without pressing any key.
Figure 4.203
4. Press the M Key to select the Control Output 1 ON/OFF Count
Alarm Set Value parameter.
Figure 4.204
5. Use the U Key to set the parameter to 10.
Figure 4.205
6. Press the O Key for at least one second to move to the Initial Setting
function group.
Figure 4.206
7. Press the O Key for at least one second to move to the Operation
function group.
Figure 4.207
amov
-169
Move to Advanced
Setting Function Group
init
off
Parameter
Initialization
ra1
0
Control Output 1
ON/OFF
Counter Alarm
Set Value
ra1
10
Control Output 1
ON/OFF
Counter Alarm
Set Value
in-t
5
Input Type
C
25
100
alm