Amov, Init, In-t – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 225

background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-89

2. Select the Move to Advanced Setting function group parameter by

pressing the

M Key.

Figure 4.202

3. Use the D Key to enter the password (“-169”). It is possible to move to

the Advanced Setting function group by either pressing the

M Key or

waiting two seconds without pressing any key.

Figure 4.203

4. Press the M Key to select the Control Output 1 ON/OFF Count

Alarm Set Value parameter.

Figure 4.204

5. Use the U Key to set the parameter to 10.

Figure 4.205

6. Press the O Key for at least one second to move to the Initial Setting

function group.

Figure 4.206

7. Press the O Key for at least one second to move to the Operation

function group.

Figure 4.207

amov

-169

Move to Advanced
Setting Function Group

init

off

Parameter
Initialization

ra1

0

Control Output 1
ON/OFF
Counter Alarm
Set Value

ra1

10

Control Output 1
ON/OFF
Counter Alarm
Set Value

in-t

5

Input Type

C

25

100

alm