Sub3, Auxillary output 3 assignment – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 323
Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions
5-95
Note:
If the Standard or Heating/Cooling parameter is set to heating/cooling
control, this parameter will automatically be set to c-o (900-TC32).
Related Parameters
• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
(Initial Setting function group)
Auxillary Output 3 Assignment
Conditions of Use:
Auxiliary Output 3 must be assigned (900-TC8 only).
Function:
This parameter allows you to configure the function assigned to
Auxiliary Output 3.
Table 5.DN
Auxiliary Output 2 Function
Default
none:
No function is assigned to auxiliary output 2
alm2➌
(see note to
follow)
o:
Heating Control Output is output
c-o:
Cooling Control Output is output
➊
alm1:
Alarm 1is output
alm2:
Alarm 2 is output
alm3:
Alarm 3 is output
p.end:
Program end is output
➋
ralm:
Control output ON/OFF count alarm
➋
➊ If
c-o
is assigned for standard control, a value equivalent to 0% will be output.
➋ Can be selected only when the program pattern is not set to OFF.
➌ If the Standard or Heating/Cooling parameter is set to heating/cooling control when there is no Control
Output 2 (900-TC16), control automatically switches to
c-o
.
sub3