Parameter Adjustments & Application Considerations
4-57
EXAMPLE
Operating Procedure
Use the following procedure to set the manipulated variable in Manual mode.
Figure 4.111
1. Press the O key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.112
2. Select the PID ON/OFF parameter by pressing the M key and select
PID mode.
Figure 4.113
3. Select the Move to Advanced Setting function group parameter by
pressing the
M key.
Figure 4.114
Press the
D key to enter the password (−169), and move from the Initial
Setting function group to the Advanced Setting function group.
Figure 4.115
C
25
100
PV/SP
in-t
5
Input type
cntl
pid
amov
0
Move to Advanced
Setting Function Group
init
off
Parameter
initialization