Init, Lbal, Lbab – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 188

Publication 900-UM007D-EN-E - January 2011
4-52
Parameter Adjustments & Application Considerations
5. Press the D key to enter the password (−169), and move from the
Initial Setting function group to the Advanced Setting function group.
Figure 4.101
6. Select the LBA Detection Time parameter by pressing the M key.
Figure 4.102
7. Press the U key to set the parameter to 10.
Figure 4.103
8. Select the LBA Level parameter by pressing the M key.
Figure 4.104
9. Press the U key to set the parameter to 8.0. (Note: The default is 8.0.)
10. Select the LBA Band parameter by pressing the M key.
Figure 4.105
11. Press the U or D key to set the parameter to 3.0. (Note: The default is
3.0.)
Figure 4.106
init
off
Parameter
initialization
lba
0
LBA detection
time
C
lba
10
C
lbal
8.0
LBA level
C
lbal
8.0
C
lbab
3.0
LBA band
C
lbab
3.0