Publication 900-UM007D-EN-E - January 2011

5-86

Parameter Functions & Definitions

Alarm 1 OFF Delay

Alarm 2 OFF Delay

Alarm 3 OFF Delay

Conditions of Use:

Alarm 1 must be assigned, and the Alarm 1 Type

parameter must NOT be 0, 12, or 13. Alarm 2 must be assigned, and the
Alarm 2 Type parameter must NOT be 0, 12, or 13. Alarm 3 must be assigned,
and the Alarm 3 Type parameter must NOT be 0, 12, or 13.

Function:

Alarm 1, 2, or 3 outputs are prevented from turning OFF until

after the delay time you configure in these parameters has elapsed.

• To enable the alarm set the OFF delay to some value >0.
• To disable the OFF delay, set 0.

Related Parameter

• Alarm 1…3 Type (Initial Setting function group, page 5-59)

Input Shift Type

Conditions of Use:

The sensor Input Type must be a thermocouple or

resistance thermometer (RTD) input.

Function:

This parameter allows you to configure the shift method for

thermocouple or resistance thermometer inputs.

• When the Input Type is thermocouple or resistance thermometer, set

either a 1-point shift or a 2-point shift.

Table 5.CZ

Configurable Range

Units

Default

0…999

Seconds

0

Table 5.DA

Selections

Default

ins1: 1-point shift, ins2: 2-point shift

ins1

a1of
a2of
a3of

istp